Open motor winding

An internal winding path is broken, preventing intended motor operation.

What happens

An internal winding path is broken, preventing intended motor operation.

Typical symptoms

No start or hum despite appropriate supply and start components.

Checks that distinguish this cause

After safe isolation, identify the actual terminal scheme and separate the harness. Compare winding tests with model data, accounting for an internal protector that may be open while hot.

What can look similar

A hot overload or broken external lead can look like an open winding.

Repair direction

Replace a confirmed failed hermetic compressor using the approved refrigeration procedure and investigate the original stress.

Verify the repair

Verify supply, starting, current and refrigeration performance after repair.

Equipment-specific limits

Single-phase C/R/S checks do not apply to every inverter or three-phase compressor. Use model data, isolate electronics as directed and never run or perform insulation tests under vacuum.