Control transformer · CAUSE ARTICLE

Open secondary winding

A break in the secondary path prevents the control load from receiving power.

What happens

A break in the secondary path prevents the control load from receiving power.

Typical symptoms

Normal input but no usable secondary output; downstream controls remain dead.

Checks that distinguish this cause

Separate the transformer terminals from the downstream harness in the documented isolated state. Test output and winding integrity using the manufacturer's procedure.

What can look similar

A loose secondary terminal or an open R conductor can imitate a winding failure. Output that returns when the load is disconnected suggests a load fault.

Repair direction

Repair external connections if they are the break; replace the transformer only when the internal failure is established.

Verify the repair

Verify output at the transformer and R-to-C at the remote controls during a call.

Equipment-specific limits

Read the primary taps, secondary rating, VA capacity and protection arrangement. A normal unloaded voltage can differ from the rated loaded voltage. There is no universal winding-resistance value.