Refrigerant circuit and charge · CAUSE ARTICLE

Excess refrigerant charge

More refrigerant than the approved system charge changes the circuit's operating balance.

What happens

More refrigerant than the approved system charge changes the circuit's operating balance.

Typical symptoms

Performance deteriorates after charging; abnormal operating readings may appear despite adequate airflow.

Checks that distinguish this cause

Use the model procedure with the correct stage, line length and stable conditions. Rule out condenser airflow faults before concluding that high pressure means overcharge.

What can look similar

Noncondensables, heat recirculation and a failed fan can create overlapping symptoms.

Repair direction

Recover and establish the approved charge using the required method; do not vent refrigerant.

Verify the repair

Record stabilized temperature/pressure measurements and capacity after correction.

Equipment-specific limits

Qualified personnel must use the identified refrigerant, approved tools and OEM charging procedure. For blends, use the correct dew/bubble convention for the calculation. A pressure reading alone does not establish charge.