Refrigerant circuit and charge · CAUSE ARTICLE

Leak or insufficient refrigerant

A leak or incomplete commissioning charge reduces the refrigerant available to the circuit.

What happens

A leak or incomplete commissioning charge reduces the refrigerant available to the circuit.

Typical symptoms

Long cooling runs, reduced capacity or an abnormal temperature/pressure pattern after airflow is confirmed.

Checks that distinguish this cause

Confirm refrigerant identity, load and airflow; compare stable measurements with the model charging method. Locate a suspected leak with the approved leak-test procedure instead of treating topping up as a repair.

What can look similar

A restriction, low indoor load or airflow fault can also produce low suction pressure.

Repair direction

Repair the verified leak, perform the specified integrity and evacuation checks, then charge by the approved method with recovery practices.

Verify the repair

Verify leak integrity and stable performance under the specified charging conditions.

Equipment-specific limits

Qualified personnel must use the identified refrigerant, approved tools and OEM charging procedure. For blends, use the correct dew/bubble convention for the calculation. A pressure reading alone does not establish charge.