What happens
Duct restrictions or leakage prevent the useful air delivery needed for comfort and coil loading.
Typical symptoms
Some rooms remain warm, unusual return noise or measured airflow outside the system requirement.
Checks that distinguish this cause
Check accessible return and supply paths, dampers and leakage; compare static pressure and measured flow with the unit's airflow tables.
What can look similar
An oversized system can also make uneven comfort and short cycles; diagnose delivery before resizing equipment.
Repair direction
Correct the verified duct or distribution defect with an appropriate design.
Verify the repair
Verify delivered airflow and room performance under representative conditions.
Equipment-specific limits
Thaw ice safely and establish airflow before charge diagnosis. Never chip ice or operate cooling indefinitely without the blower.