Evaporator coil and filter · CAUSE ARTICLE

Dirty filter or plugged indoor coil

A restricted air path reduces heat transfer and may lower coil temperature enough to freeze moisture.

What happens

A restricted air path reduces heat transfer and may lower coil temperature enough to freeze moisture.

Typical symptoms

Weak airflow, long run time or ice on the indoor coil and suction line.

Checks that distinguish this cause

Inspect the isolated filter and both accessible coil faces; assess static pressure and airflow after thawing. Confirm the filter specification and approved cleaning method.

What can look similar

A stopped blower or refrigerant shortage can also produce ice. Ice itself is not proof of low charge.

Repair direction

Renew the approved filter and clean the verified restriction without damaging fins or electronics.

Verify the repair

Confirm correct airflow and no renewed ice under stable cooling conditions.

Equipment-specific limits

Thaw ice safely and establish airflow before charge diagnosis. Never chip ice or operate cooling indefinitely without the blower.