What happens
A loose or corroded connection restricts current without being completely open.
Typical symptoms
Thermostat resets, relays chatter or controls work unloaded but fail when a coil picks up.
Checks that distinguish this cause
A qualified technician compares voltage before and after the connection during the failing load condition. Inspect and repair with power isolated. An unloaded continuity test may miss the fault.
What can look similar
Excess transformer loading also lowers control voltage, but does not necessarily localize a drop to one splice.
Repair direction
Renew the damaged connection using approved connectors and the specified termination method.
Verify the repair
Confirm the localized drop is resolved and the load remains energized reliably.
Equipment-specific limits
This guide addresses conventional R, C, Y, G, O/B and Y2 circuits. Communicating buses require their own service procedure; never apply jumpers to unidentified terminals.