TXV and metering device · CAUSE ARTICLE

Restricted valve or liquid feed

A restriction limits liquid delivery to the evaporator.

What happens

A restriction limits liquid delivery to the evaporator.

Typical symptoms

Reduced capacity and a starved-evaporator pattern under known conditions.

Checks that distinguish this cause

Verify liquid availability, airflow, superheat and subcooling using the model procedure. Compare conditions along the liquid path to localize a restriction before replacing the valve.

What can look similar

Insufficient charge can also starve the evaporator; a valve cannot feed liquid it is not receiving.

Repair direction

Correct the proven restricted component using the approved clean-system and replacement procedure.

Verify the repair

Confirm stable refrigerant feed and model-appropriate operating measurements.

Equipment-specific limits

Identify TXV, fixed orifice or electronic expansion valve. Do not use TXV adjustment as a shortcut around airflow, charge or liquid-supply faults.