What happens
The relay cannot actuate because its coil has failed or the intended command is absent.
Typical symptoms
Cooling demand exists but the indoor fan fails to join.
Checks that distinguish this cause
Trace the command and measure across the documented coil terminals using the authorized procedure. Isolate before comparing coil resistance with its specification.
What can look similar
An open G conductor or thermostat output fault can prevent pickup without a failed relay.
Repair direction
Repair the missing command or replace the confirmed failed approved relay.
Verify the repair
Verify fan-only and cooling calls with correct blower response.
Equipment-specific limits
Some control boards contain an integrated relay; ECM controls may not use this conventional arrangement.