What happens
Weather damage, loose clips or terminals add series resistance to the supply path.
Typical symptoms
Starts fail under load although unloaded voltage seems normal; discoloration or heat near a terminal.
Checks that distinguish this cause
Inspect the isolated assembly and evaluate localized voltage drop during an authorized live test. Examine both poles and fuse clips.
What can look similar
Pitted contactor poles or a loose whip connection can make the same symptom downstream.
Repair direction
Replace damaged approved disconnect parts and correct water entry or installation defects.
Verify the repair
Verify load voltage and reliable starts with no abnormal connection heating.
Equipment-specific limits
The line side can remain energized with the pullout removed. A non-fused disconnect has no fuse to test.