What happens
Poor contact at the fuse clips creates a series resistance and heating.
Typical symptoms
Power returns when disturbed, or the thermostat blanks only under a call; a removed fuse tests intact.
Checks that distinguish this cause
Inspect clips and terminals with power isolated. Where appropriate, a qualified technician checks the voltage drop across the holder during load.
What can look similar
A weak transformer can mimic supply collapse. An intact fuse does not establish that its holder is healthy.
Repair direction
Service or replace the holder using approved parts; do not bend or bypass damaged contacts as a permanent repair.
Verify the repair
Verify stable control voltage under load and absence of abnormal holder heating.
Equipment-specific limits
A fuse is evidence of an event, not its explanation. Match the exact type and rating specified for the equipment.